E2810 Drive system not ready for operation

Cause
Error message of one or several drives of a drive
system
One or several drives still are in communication
phase 2
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
Supported by Supply Unit:
One or several drives of a "drive system" (devices interconnected via DC
bus and module bus) are signaling a drive error via the module bus and
the supply is not yet ready for power output. As long as the error keeps
being signaled, it is impossible to switch power on.
The supply unit or converter is signaling E2810 Drive system not ready
for operation on the display.
Remedy
Identify drive or drives signaling an error. Remove cause
of error at respective drive or drives
Switch drives to communication phase 4 ["ready for
operation" (bb) or "drive ready" (Ab)]
See also Functional Description "Power Supply"