E2076 Measuring Encoder: Encoder Signals Disturbed - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
8-38
Warning Diagnostic Messages (Exxxx)

E2076 Measuring encoder: encoder signals disturbed

Cause
Defective encoder cable or cable shielding
Measuring system defective
Faulty mounting of measuring head in the case of
linear measuring systems
Measuring system dirty
Hardware defect on control section of drive
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
The hardware checks the signals of the measuring encoder for
inadmissible signal dips. If a signal (e. g. sin or cos) leaves the thresholds
monitored by the hardware, the warning E2076 is generated.
In the case of major failures or several signal dips in series, the error
F2043 Measuring encoder: encoder signals incorrect is generated
and the drive is shut down. The warning E2076 therefore points at
disturbed encoder signals before a breakdown occurs.
Note:
The warning E2076 is only cleared by reinitialization of the
encoder
position;
communication phase 2.
Remedy
Check cable to measuring system and replace it, if
necessary
Check measuring system and replace it, if necessary
Check mounting of measuring head and correct it, if
necessary
Clean or replace measuring system
Replace control section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
E2076 - Attributes
Display:
E2076
Mess. no.:
E2076 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
i. e.
it
is
necessary
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
to
switch
to