F3142 Activation Time Of Enabling Control Exceeded - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
7-68
Error Messages

F3142 Activation time of enabling control exceeded

Cause
Parameterized activation time has been exceeded.
Parameterization of P-0-3222, Max. activation time
of enabling control does not make sense
Enabling control is defective or incorrectly wired
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
The parameterized maximum time for the activation of the enabling
control (P-0-3222, Max. activation time of enabling control) has been
exceeded.
The drive is shut down according to the setting in P-0-0119, Best
possible deceleration.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Remedy
Change parameterization of P-0-3222, Max. activation
time of enabling control in useful way
Check and, if necessary, replace/correct enabling
control and wiring
After having removed the cause start command S-0-0099, C0500 Reset
class 1 diagnostics in order to clear error and then set drive enable
again.
F3142 - Attributes
Display:
F3142
Mess. no.:
F3142 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P