C0104 Config. Idn For Mdt Not Configurable - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
Rexroth IndraDrive

C0104 Config. IDN for MDT not configurable

Cause
in the S-0-0015, Telegram type parameter the
telegram type 7 (configured telegram) was set
in S-0-0024, Config. list of the master data
telegram there were some parameters entered that
are not contained in S-0-0188, List of configurable
data in the MDT
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
During
the
transition
communication phase 3 (C0100) an error with regard to the telegram
configuration of the master communication was detected.
Remedy
set priority telegram (telegram type = 0..6) in S-0-0015,
Telegram type parameter
in S-0-0024, Config. list of the master data telegram
those parameters have to be entered that are contained
in S-0-0188, List of configurable data in the MDT
Note:
List parameters are only allowed in the multiplex channel.
C0104 - Attributes
Display:
C0104
Mess. no.:
C0104 (hex)
Command Diagnostic Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
check
from
communication
9-19
phase 2
to