F2818 Phase Failure; F2819 Mains Failure - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
7-122
Error Messages

F2818 Phase failure

Cause
Mains circuit breaker defective
Incorrect wiring

F2819 Mains failure

Cause
Mains failure (permanent or temporary)
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Supply Unit:
A single-phase mains failure of more than 2 seconds was detected. The
device was switched off.
Remedy
Replace mains circuit breaker
Check and correct wiring
F2818 - Attributes
Display:
F2818
Mess. no.:
F2818 (hex)
Supported by Firmware Variant:
Supported by Supply Unit:
The mains has failed. The DC bus voltage has fallen below a threshold
value so that a new soft start process is required.
Remedy
Search and remove cause of mains failure
See also Functional Description "Power Supply"
F2819 - Attributes
Display:
F2819
Mess. no.:
F2819 (hex)
Rexroth IndraDrive
HMV01
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
HMV01
DOK-INDRV*-GEN-**VRS**-WA01-EN-P

Hide quick links:

Table of Contents
loading

Table of Contents