F8806 Timeout During Loading Process; F8813 Connection Error Mains Choke - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
Rexroth IndraDrive

F8806 Timeout during loading process

Cause
Too many additional capacitances were connected
There is short circuit or load of low impedance in DC
bus

F8813 Connection error mains choke

Cause
Mains choke was incorrectly connected
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
F8203 - Attributes
Display:
F8203
Mess. no.:
F8203 (hex)
Supported by Supply Unit:
During the loading of the DC bus before switching on the power supply
("soft start") the expected DC bus voltage could not be reached within a
time window.
Remedy
Reduce number of additional capacitance modules
Check wiring of DC bus connection
F8806 - Attributes
Display:
F8806
Mess. no.:
F8806 (hex)
Supported by Supply Unit:
After the power supply had been switched on a wiring error of the mains
choke (e.g. incorrect phase sequence of the mains phases) was detected.
Remedy
Check and correct connection of mains choke
F8813 - Attributes
Display:
F8813
Mess. no.:
F8813 (hex)
Error Messages
HMV01
HMV01
7-27