Commissioning
7.2

Commissioning Process

Step
Rotate the potentiometer counterclock‐
1
wise (leftwards) to the greatest extent
2
Press Run key
Rotate the potentiometer clockwise
(rightwards) slowly and the displayed
3
value starts to change, until 5.00 is dis‐
played
Observe:
● Whether the motor runs in the correct
direction
4
● Whether the motor runs smoothly
● Whether there is any abnormal noise
or problem
Rotate the potentiometer clockwise
5
(rightwards)
Rotate the potentiometer counterclock‐
6
wise (leftwards)
7
Press Stop key
Fig.7-1: Commissioning process
48/235
Operation
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Description
The initial frequency value is 0.00
Enter the command for running, with
0.00 displayed
The motor starts to run
Observe the running, and immediately
stop the motor by shutting off the pow‐
er if any abnormality occurs. Restart
commissioning only after the fault
causes have been removed
The motor accelerates
The motor decelerates
When commissioning is complete, the
command for stopping is activated.
The frequency converter is ready for
normal operation.