Bosch Rexroth EFC 3600 Operating Instructions Manual page 107

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
When the output current exceeds the threshold defined in [E1.10] for delay time defined
in [E1.12], the function is active. The signal is immediately deactivated when the output
current is lower than the threshold defined in [E1.10].
E1.13
Middle count value
Setting range
0 ~ [E1.14]
Minimum unit
1
Factory default
0
E1.14
Target count value
Setting range
[E1.13] ~ 9999
Minimum unit
1
Factory default
0
The corresponding digital output for "Middle / Target count value reached" should be
configured, see more details in [E1.00] and [E1.02].
After the counter has reached its Middle /Target value [E1.13] / [E1.14], it remains at
this value until it is reset by a valid edge of the input terminal signal parameterized as
"clear counting". As long as the counter value is not reset, the digital outputs configured
as "DOutx=16: Target counter value reached" and "DOutx=17: Middle counter value
reached" remain active. These signals are reset by the next valid triggering edge of the
input terminal signal parameterized as "counting signal input" after the counter value is
cleared.
● If one of the parameters [E1.13], [E1.14] and / or digital input terminal
configuration [E0.01] ~ [E0.05] is changed, the counter value is reset
and digital outputs defined as "DOutx=16: Target counter value
reached" and "DOutx=17: Middle counter value reached" are switched
to be inactive immediately;
● The maximum allowed frequency of digital input is 50 Hz and the mini‐
mum allowed pulse width (both active and inactive) should be longer
than 8ms.
E1.30
FM1 analog output selection
Setting range
0 ~ 7
Minimum unit
1
Factory default
0
E1.31
FM1 channel mode
Setting range
0: 0 ~ 10 V; 1: 2 ~ 10 V
Minimum unit
1
Factory default
0
E1.32
FM1 gain setting
Bosch Rexroth AG
Parameter Settings
105/235