Bosch Rexroth EFC 3600 Operating Instructions Manual page 106

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents
Bosch Rexroth AG
Parameter Settings
the output frequency is lower than the value set by "([E1.05] or [E1.07]) - (E1.06] or
[E1.08])".
Fig.8-38: Frequency detection level
E1.09
Frequency converter overload pre-warning level setting
Setting range
20.0 % ~ 200.0 % (Rated frequency converter current)
Minimum unit
0.1 %
Factory default
110.0 %
E1.10
Motor pre-warning level setting
Setting range
100.0 % ~ 250.0 % (Rated motor current)
Minimum unit
0.1 %
Factory default
100.0 %
When the output current exceeds the threshold defined in [E1.09] for delay time defined
in [E1.11], the function is active. The signal is immediately deactivated when the output
current is lower than the threshold defined in [E1.09].
E1.11
Frequency converter overload pre-warning delay
Setting range
0.0 ~ 20.0s
Minimum unit
0.1s
Factory default
2.0s
E1.12
Motor overload pre-warning delay
Setting range
0.0 ~ 20.0s
Minimum unit
0.1s
Factory default
2.0s
104/235
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Table of Contents
loading