Bosch Rexroth EFC 3600 Operating Instructions Manual page 135

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Error
Error name Possible reason
code
E-St
RS-
CF
OT
CPUd
External fault caused by input
signals via external terminals
Wrong wiring/ setting of multi-
function external terminals
Device connection problem
Improper baud rate setting
The offset is out of range due
to EMC or defect of current
detection
Motor over heat
Temperature sensor defect
Improper protection level
CPU is disturbed by external
noise and program run to ille‐
gal address
Bosch Rexroth AG
Solution
Check external terminal status,
check respective reason to fault
Ensure the right external signals
have been connected correctly to
the right multi-function external
terminals which are assigned for
external fault input
([E0.01]~[E0.05]=19,20)
Check device communication
connection
Set proper baud rate
● Remove the EMC problem
If it fails again, replace the fre‐
quency converter
● Provide a better cooling condi‐
tion
● Check the load
Replace the motor
Different motor with different max‐
imum temperature, configure the
external division circuit and
choose protection level [S2.22]
Check the wiring of control circuit,
main circuit and ground to find out
the source of interference
Diagnosis
133/235