Efc 3600 Basic Parameter Fast Settings - Bosch Rexroth EFC 3600 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents
Bosch Rexroth AG
Commissioning
7.3

EFC 3600 Basic Parameter Fast Settings

Using the operating panel to set the necessary parameters based on the application
loads and specifications allows the frequency converter to start rapidly. A basic generic
parameter fast setting table is given below.
● Set [b0.02]=4 with Func and Set keys to show "-St-" group.
● For parameter attributes, see
Symbols in Parameter Tables" on page
Function
Name
code
[b0.21] Carrier frequency
[b1.00] First frequency set‐
ting source
[b1.02] First Run command
source
[b1.05] Max. frequency
[b1.06] Upper frequency
[b1.07] Lowest frequency
[b1.04] Digital set frequency
[b1.10] Direction control
[b1.20] Acceleration time 1
[b1.21] Deceleration time 1
[b1.22] Acceleration/deceler‐
ation curve mode
[b1.30] Starting mode
[b1.40] Stopping mode
[S0.00] V/F curve mode
[S2.00] Rated motor frequen‐
cy
[S2.01] Rated motor rotation
speed
[S2.02] Rated motor power
50/235
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
chapter 17.2.1 "Description of Attribute
Setting
Min.
range
1 ~ 15 kHz
1 kHz
0 ~ 6
0 ~ 2
50.00 ~ 400.00
0.01 Hz
Hz
[b1.07] ~ [b1.05] 0.01 Hz
0.00 ~ [b1.06]
0.01 Hz
[b1.07] ~ [b1.06] 0.01 Hz
0 ~ 3
0.1 ~ 6000.0s
0.1s
0.1 ~ 6000.0s
0.1s
0 ~ 1
0 ~ 2
0 ~ 2
0 ~ 2
5.00 ~ 400.00
0.01 Hz
Hz
1 ~ 30000 rpm
1 rpm
0.1 ~ 1000.0 kW 0.1 kW
195.
Factory
unit
default
4 kHz
1
0
1
0
50.00 Hz
50.00 Hz
0.00 Hz
50.00 Hz
1
0
5.0s
5.0s
1
0
1
0
1
0
1
0
50.00 Hz
Depending
on model
Depending
on model
Attributes
Run/Stop
Stop
Stop
Stop
Run/Stop
Run/Stop
Run/Stop
Stop
Run/Stop
Run/Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Table of Contents
loading

Table of Contents