Parameter Settings
Fig.8-23: Jogging Acc. / Dec. time
● Jogging command only comes from external terminals or communication.
● When jogging command is activated, the motor runs with predefined frequency;
when the jogging command is inactive, the motor resumes the previous status.
● If jogging forward and jogging reverse are active at the same time, the frequency
converter will STOP; if the jogging forward / reverse command is activated during
jogging reverse / forward, the frequency converter will STOP according to [b1.40]
"Stopping mode".
S3.05
Skip frequency 1
Setting range
0.00 Hz ~ [b1.06]
Minimum unit
0.01 Hz
Factory default
0.00 Hz
S3.06
Skip frequency 2
Setting range
0.00 Hz ~ [b1.06]
Minimum unit
0.01 Hz
Factory default
0.00 Hz
S3.07
Skip frequency 3
Setting range
0.00 Hz ~ [b1.06]
Minimum unit
0.01 Hz
Factory default
0.00 Hz
S3.08
Skip frequency range
Setting range
0.00 ~ 30.00 Hz
Minimum unit
0.01 Hz
Factory default
0.00 Hz
To avoid the mechanical resonance, this function is implemented to define 3 skip fre‐
quencies. 3 skip frequencies are supported as shown in the figure below: