Restore Parameters To Factory Defaults - Bosch Rexroth EFC 3600 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Function
Name
code
[S2.03] Rated motor voltage
[S2.04] Rated motor current
Fig.7-2: Basic parameter fast setting
7.4

Restore Parameters to Factory Defaults

If the frequency converter fails to run the motor due to incorrect parameter settings, a
simple solution is to initialize the parameters to factory defaults. Setting [b0.05]=1 will
start initialization.
Please be sure that the parameter settings match with the motor and the field applica‐
tions after factory defaults restore. Adjust the parameter settings after factory defaults
restore if necessary.
Operating frequency
Acc./Dec. time
Protection mode in case
of motor overload and
overheat
Panel operation
V/F curve mode
Fig.7-3: Factory defaults
Setting
range
0 ~ 480 V
0.1 ~ 1000.0 A
Set by the potentiometer ([b1.00])
Linear, Acc. for 5s / Dec. for 5s ([b1.20], [b1.21])
Motor rated current [S2.04], thermal motor time constant
[S2.23], low speed derating frequency [E4.04], and zero
speed load [E4.05]
Run, Stop buttons as commands, potentiometer as frequen‐
cy setting source
linear
Bosch Rexroth AG
Commissioning
Min.
Factory
unit
default
1 V
Depending
on model
0.1 A
Depending
on model
Attributes
Stop
Stop
51/235