Condition as supplied, identification, transport and
storage
5.1

Condition as supplied

5.1.1

Factory testing

Voltage testing and insulation resistance testing

5.1.2

Customer testing

Condition as supplied, identification, transport and storage

According to standard, the components of the Rexroth IndraDrive Cs range
are tested with voltage.
Testing
Voltage testing
Insulation resistance testing
Tab. 5-1:
Applied standards
NOTICE
Before conducting voltage testing or insulation resistance testing for an instal‐
lation or machine in which these components are used:
Disconnect all connections to the Rexroth components or disconnect the
plug-in connections to protect the electronic components.
Bosch Rexroth AG
Test rate
100% (EN 61800-5-1)
100% (EN 60204-1)
Risk of damage to the installed Rexroth com‐
ponents by customer-side testing of the ma‐
chine or installation!