C0723 Safety command for load defaults procedure incorrect

Cause
Internal command for channel 2 was incorrectly
executed
Channel 2 is executing another internal command
that mustn't be interrupted
Hardware defect on optional safety technology
module
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
With the command C07_2 Load def. proc. com. (load def. pr. for
safety techn.) the safety parameters of channel 1 are set to default
values and an internal command is started so that channel 2 accepts the
default values. The safety technology is deactivated by the command
because valid safety parameters are no longer available. The safety
technology is in its condition as supplied.
Remedy
Clear command C07_2 Load def. proc. com. (load def.
pr. for safety techn.) and then restart it.
If error is signaled again, reset optional safety
technology module (switch control voltage off and then
on again)
Complete internal command that is still running
Restart C07_2 Load def. proc. com. (load def. pr. for
safety techn.). If command error occurs repeatedly,
replace control section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
C0723 - Attributes
Display:
C0723
Mess. no.:
C0723 (hex)
Command Diagnostic Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
9-77