C3204 Incorrect Input For Speed - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
9-114
Command Diagnostic Messages

C3204 Incorrect input for speed

Cause
There is no useful relation between list element 4
(rated speed) in P-0-4032, Type plate list
asynchronous motor and rated frequency, i.e.
number of pole pairs cannot be calculated
C3205 Incorrect input for power factor
Cause
Power factor of motor is outside of useful limits
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the command P-0-4033, C3200 Command
Calculate data for asynchronous motor an error was detected.
Remedy
Correct list element 4 (rated speed) in P-0-4032, Type
plate list asynchronous motor
C3204 - Attributes
Display:
C3204
Mess. no.:
C3204 (hex)
Supported by Firmware Variant:
During the execution of the command P-0-4033, C3200 Command
Calculate data for asynchronous motor an error was detected.
Remedy
List element 5 (power factor cos LQ P-0-4032, Type
plate list asynchronous motor has to be between 0.5
and 0.999
C3205 - Attributes
Display:
C3205
Mess. no.:
C3205 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P