7-20
Error Messages

F8102 Error when initializing power section

Cause
Hardware and firmware do not match
Parameter P-0-1510, Circuit board code power
section stored on power section is invalid or was
incorrectly written
Hardware defect on power section

F8118 Invalid power section/firmware combination

Cause
Inappropriate firmware
Inappropriate power section
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
During the initialization of the drive the power section is checked for
correct function. An error was detected during this check.
Remedy
Check Firmware Release Notes or Firmware Version
Notes and, if necessary, use latest firmware release
Switch drive off and on again. If error occurs again,
check content of P-0-1510, Circuit board code power
section and contact our service department!
Maybe you have to replace power section or entire drive
controller
Replace power section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
F8102 - Attributes
Display:
F8102
Mess. no.:
F8102 (hex)
Supported by Firmware Variant:
The power section is incompatible with the firmware used.
Remedy
Use firmware that matches power section
Use power section that matches firmware
F8118 - Attributes
Display:
F8118
Mess. no.:
F8118 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P

Hide quick links:

Table of Contents
loading

Table of Contents