F3135 Dynamization Pulse Width Incorrect - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
7-66
Error Messages

F3135 Dynamization pulse width incorrect

Cause
Error in wiring of dynamization
Error in signal shape of dynamization signal in the
case of external dynamization
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
The drive is shut down according to the setting in P-0-0119, Best
possible deceleration.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Remedy
Remove error in wiring of dynamization
Use appropriate signal source in the case of external
dynamization
After having removed the cause start command S-0-0099, C0500 Reset
class 1 diagnostics in order to clear error and then set drive enable
again.
Note:
If error message occurs repeatedly, safety technology
firmware has to be replaced.
- or -
Control section (only by Rexroth service engineers or
especially trained users) or entire drive controller has to be
replaced. The replacement of the entire drive controller is
described in the Project Planning Manual for the power
section.
F3135 - Attributes
Display:
F3135
Mess. no.:
F3135 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P