F2033 External Power Supply X10 Error - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
Rexroth IndraDrive

F2033 External power supply X10 error

Cause
Voltage externally applied is outside of allowed
range [and temporary failures (voltage peaks) are
detected]
At least one of the inputs was connected with
reversed polarity
At least one of the outputs has short circuit
At least one of the outputs is overloaded
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
If the X10 interface at the IndraDrive M controller has been equipped with
a digital I/O extension, this requires an external 24 V power supply.
Remedy
Supply interface with controlled power supply unit
Check wiring
Check wiring
Supply motor brake and interface with different power
supply units, especially in the case of long motor cables
F2033 - Attributes
Display:
F2033
Mess. no.:
F2033 (hex)
Error Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
7-89