C0156 Field Bus: Idn For Cycl. Actual Val. Not Configurable; C0157 Field Bus: Length For Cycl. Actual Values Exceeded - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
Rexroth IndraDrive

C0156 Field bus: IDN for cycl. actual val. not configurable

Cause
In operating data of P-0-4080, Field bus: config.
list of cyclic command value data ch. there is an
IDN that is not contained in S-0-0187, List of
configurable data in the AT

C0157 Field bus: length for cycl. actual values exceeded

Cause
Sum of data widths of all IDNs entered in P-0-4080,
Field bus: config. list of cyclic actual value data
ch. is exceeding max. value of P-0-4082, Field bus:
length of cyclic actual value data channel
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the command S-0-0127, C0100 Communication
phase 3 transition check an error with regard to the telegram
configuration of the master communication was detected.
Remedy
In P-0-4080, Field bus: config. list of cyclic command
value data ch. enter allowed IDNs (cf. S-0-0187, List of
configurable data in the AT)
Note:
List parameters are only allowed in the multiplex channel.
For removing command errors see "Command Errors"
C0156 - Attributes
Display:
C0156
Mess. no.:
C0156 (hex)
Supported by Firmware Variant:
During
the
transition
communication phase 3 (C0100) an error with regard to the telegram
configuration of the master communication was detected.
Remedy
Reduce number of IDNs entered in P-0-4080, Field
bus: config. list of cyclic actual value data ch.
C0157 - Attributes
Display:
C0157
Mess. no.:
C0157 (hex)
Command Diagnostic Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
check
from
communication
9-43
phase 2
to