C0154 Field Bus: Idn For Cycl. Command Val. Not Configurable; C0155 Field Bus: Max. Length For Cycl. Command Val. Exceeded - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
9-42
Command Diagnostic Messages

C0154 Field bus: IDN for cycl. command val. not configurable

Cause
In operating data of P-0-4081, Field bus: config.
list of cyclic command value data ch. there is an
IDN that is not contained in S-0-0188, List of
configurable data in the MDT

C0155 Field bus: max. length for cycl. command val. exceeded

Cause
Sum of data widths of all IDNs entered in P-0-4081,
Field bus: config. list of cyclic command value
data ch. is exceeding max. value of P-0-4071, Field
bus: length of cyclic command value data
channel
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the command S-0-0127, C0100 Communication
phase 3 transition check an error with regard to the telegram
configuration of the master communication was detected.
Remedy
In P-0-4081, Field bus: config. list of cyclic command
value data ch. enter allowed IDN (cf. S-0-0188, List of
configurable data in the MDT)
For removing command errors see "Command Errors"
C0154 - Attributes
Display:
C0154
Mess. no.:
C0154 (hex)
Supported by Firmware Variant:
During
the
transition
communication phase 3 (C0100) an error with regard to the telegram
configuration of the master communication was detected.
Remedy
Reduce number of IDNs entered in P-0-4081, Field
bus: config. list of cyclic command value data ch.
C0155 - Attributes
Display:
C0155
Mess. no.:
C0155 (hex)
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
check
from
communication
DOK-INDRV*-GEN-**VRS**-WA01-EN-P