F6042 Both Travel Range Limit Switches Activated - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
7-46
Error Messages

F6042 Both travel range limit switches activated

Cause
Due to incorrect mounting, axis activates both travel
range limit switches simultaneously
Travel range limit switches were incorrectly
connected
Switching logic of travel range limit switches does
not correspond to realized wiring
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
The compliance with the allowed travel range of linear axes is monitored
on the hardware side via two travel range limit switches. When the travel
range has been exceeded, one of the two limit switches is activated, if the
limit switches were correctly mounted.
The error F6042 is generated, if
the controller detects that both travel range limit switches have been
simultaneously activated and
exceeding the travel range is handled as an error (setting in
P-0-0090, Travel range limit parameter).
Remedy
Mount travel range limit switches in such a way that they
are activated shortly before axis end position is reached.
Make sure the braking distance is sufficient
Connect travel range limit switches correctly; check
compliance with switching logic set in P-0-0090, Travel
range limit parameter
Check switching logic with regard to realized wiring,
adjust it in P-0-0090, Travel range limit parameter, if
necessary
F6042 - Attributes
Display:
F6042
Mess. no.:
F6042 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P