F3146 System Error Channel 2 - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
Rexroth IndraDrive

F3146 System error channel 2

Cause
System error on channel 2
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
The drive is shut down according to the setting in P-0-0119, Best
possible deceleration.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Remedy
Reset module by switching control voltage on and off.
Start command S-0-0099, C0500 Reset class 1
diagnostics in order to clear error an then set drive
enable again.
If error occurs repeatedly, replace control section or
entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.