C0125 Error When Reading Encoder Data => Optional Encoder - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents
9-30
Command Diagnostic Messages
C0125 Error when reading encoder data => optional encoder
Cause
Measuring system cable defective
Measuring system defective
Encoder interface card defective
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Supported by Firmware Variant:
During
the
transition
communication phase 3 (C0100) an error during the reading of the
encoder data from the data memory of the optional encoder was
detected.
Note:
Measuring systems with their own data memory are DSF/HSF
and resolvers, as well as measuring systems with EnDat
interface (Heidenhain company) and HIPERFACE interface
(Stegmann company).
Remedy
Check measuring system cable
Replace measuring system
Replace encoder interface card
C0125 - Attributes
Display:
C0125
Mess. no.:
C0125 (hex)
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
check
from
communication
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Rexroth IndraDrive
phase 2
to

Hide quick links:

Table of Contents
loading

Table of Contents