Transporting The Components - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
120/341
Bosch Rexroth AG
Condition as supplied, identification, transport and storage
5.3

Transporting the components

Description
Temperature range
Relative humidity
Absolute humidity
Climatic category (IEC 721)
Moisture condensation
Icing
5.4
Storing the components
Description
Temperature range
Relative humidity
Absolute humidity
Climatic category (IEC 721)
Moisture condensation
Icing
Ambient and operating conditions for transport
Symbol
Unit
T
°C
a_tran
%
g/m
3
Tab. 5-3:
Ambient and operating conditions for transport
NOTICE
Some components contain electrolytic capacitors which may deteriorate dur‐
ing storage.
When storing the following components for a longer period of time, run them
once a year for at least 1 hour:
Converters and supply units: Operated with mains voltage U
Inverters and DC bus capacitor units: Operated with DC bus voltage
U
DC
Ambient and operating conditions for storage
Symbol
Unit
T
°C
a_store
%
g/m
3
Tab. 5-4:
Ambient and operating conditions for storage
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
Value
-20 ... +70
5 ... 95
1 ... 60
2K3
Not allowed
Not allowed
Risk of damage to components from long-
term storage!
Value
-20 ... +55
5 ... 95
1 ... 29
1K3
Not allowed
Not allowed
LN