Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual page 111

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
the maximum continuous power which can be looped through via the
DC bus connector X77
(The continuous power results from the current carrying capacity of the
DC bus connector X77 and the mains voltage value.)
Load of DC Bus Connector at I = 25 A:
U
Mains voltage
LN
P
Continuous power at DC bus connector X77
X77_cont
Fig. 4-33:
Load of DC Bus Connector
V
P
LN
X77_cont
200 V AC
7 kW
400 V AC
14 kW
500 V AC
14 kW
Tab. 4-42:
Selected values of continuous power via DC bus connector X77
(P
) depending on mains voltage
X77_cont
Number of supplied devices:
If the sum of power reserves (P
the continuous power of X77 (P
vices results from P
X77_cont
the individual devices at average speed.
If the sum of power reserves (P
the continuous power of X77 (P
vices results from P
reserve
the individual devices at average speed.
Bosch Rexroth AG
Combining the individual components
) of the supplying devices is greater then
reserve
), the maximum number of supplied de‐
X77_cont
minus the respective DC bus continuous power of
) of the supplying devices is smaller than
reserve
), the maximum number of supplied de‐
X77_cont
minus the respective DC bus continuous power of
109/341