Installing Signal Lines And Signal Cables - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
Metal surfaces
Ground wires and shield connec‐

Installing signal lines and signal cables

Line routing
Shielding
you can establish the contact to varnished surfaces by using tooth lock wash‐
ers.
Always use connection elements (screws, nuts, plain washers) with a highly
conductive surface.
Highly conductive surfaces are those with bare, zinc-coated or tinned metal
surfaces.
Poorly conductive surfaces are those with anodized, yellow chromatized,
black gunmetal finished or lacquered metal surfaces.
When connecting ground wires and shield connections, what is important is
tions
not the cross section of the wire, but the area of the contact surface, since
high-frequency interference currents mainly flow on the surface of the con‐
ductor.
Always connect cable shields, especially shields for the motor power cables,
to ground potential over a large surface area.
For measures to prevent interference, see the Project Planning Manuals for
each device. We also recommend the following:
Route signal and control lines away from power cables at a minimum
distance of d5 = 100 mm
with a grounded separating sheet. The best way is to route them in sep‐
arate cable ducts. If possible, only route signal lines into the control cab‐
inet at one point.
If signal lines cross power cables, route them at an angle of 90° in order
to avoid interference injection.
Ground unused and connected spare cables at both ends at least in or‐
der to avoid an antenna effect.
Do not use more line than is necessary.
Run cables as close to grounded metal surfaces as possible (reference
potential). Closed, grounded cable ducts or metal pipes are ideal, but
are only needed to meet strict requirements (sensitive instrument leads).
Avoid suspended lines or lines routed along synthetic carriers, because
they function like reception antennas (noise immunity) and transmitting
antennas (emission of interference). Exceptional cases are flexible ca‐
ble tracks over short distances of at most 5 m.
Connect the cable shield immediately at the devices in the shortest and most
direct way possible and over the largest possible surface area.
Connect the shield of analog signal lines at one end over a large surface
area, normally in the control cabinet at the analog device. Make sure the con‐
nection to ground/housing is short and over a large surface area.
Connect the shield of digital signal lines at both ends over a large surface
area and in short form. In case of potential differences between line begin‐
ning and end, run an additional bonding conductor in parallel. This prevents
compensating current from flowing via the shield. The recommended cross
section is 10 mm
2
.
Separable connections absolutely must be equipped with connectors that
have a grounded metal housing.
In case of unshielded lines belonging to the same circuit, twist feeder and re‐
turn cable.