Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual page 44

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
42/341
Bosch Rexroth AG
Combining the individual components
Mains grounded via outer conductor
Mains voltage ≤ 3 AC 230V
No transformer required
HCS01.1E-W0003-A-02
HCS01.1E-W0006-A-02
HCS01.1E-W0009-A-02
HCS01.1E-W0013-A-02
HCS01.1E-W0018-A-02
HCS01.1E-W0005-A-03
HCS01.1E-W0008-A-03
HCS01.1E-W0018-A-03
HCS01.1E-W0028-A-03
HCS01.1E-W0054-A-03
DC bus coupling
Mains Type and Mains Voltage
IT mains
Mains voltage 3 AC 230 ... 500 V
Isolating transformer with grounded
neutral point required
HCS01.1E-W0005-A-03
HCS01.1E-W0008-A-03
HCS01.1E-W0018-A-03
HCS01.1E-W0028-A-03
HCS01.1E-W0054-A-03
Tab. 4-1:
Mains Type and Mains Voltage
Mains Supply
1-phase
1)
1 AC 110 ... 230 V
HCS01.1E-W0003-A-02
HCS01.1E-W0006-A-02
HCS01.1E-W0009-A-02
HCS01.1E-W0013-A-02
HCS01.1E-W0018-A-02
Individual supply
With 1-phase mains supply, you can connect the mains supply
1)
line to connector X3 at L1, L2 or L3
Tab. 4-2:
Mains Supply
If energy compensation is to be available between the individual devices, the
DC buses of these devices must be coupled. DC bus coupling restricts the
selection of HCS01 converters.
See also
chapter 4.6.4 "DC bus coupling" on page
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
TN-S mains
TN-C mains
TT mains
To be noticed with 1-phase mains volt‐
age: See table "Mains Supply"
HCS01.1E-W0003-A-02
HCS01.1E-W0006-A-02
HCS01.1E-W0009-A-02
HCS01.1E-W0013-A-02
HCS01.1E-W0018-A-02
HCS01.1E-W0005-A-03
HCS01.1E-W0008-A-03
HCS01.1E-W0018-A-03
HCS01.1E-W0028-A-03
HCS01.1E-W0054-A-03
3-phase
3 AC 200 ... 500 V
Autotransformer
3 AC 110 ... 230 V
HCS01.1E-W0005-A-03
HCS01.1E-W0008-A-03
HCS01.1E-W0018-A-03
HCS01.1E-W0028-A-03
HCS01.1E-W0054-A-03
Mains supply
105.
-
-
Individual supply
Group supply
Central supply

Hide quick links:

Table of Contents
loading

Table of Contents