Electrical Data Nfe / Nfd - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
Allowed Mounting Positions

Electrical Data NFE / NFD

Maximum mains con‐
Nominal
nection voltage of
mains
mains 50...60 Hz
current
I
U
nenn
N
In V
In A
AC 480V +10%
7
AC 480V +10%
16
AC 480V +10%
30
AC 480V +10%
55
AC 480V +10%
75
AC 480V +10%
130
AC 480V +10%
180
Mounting posi‐
Note
tion
G1
Allowed without restrictions
G2
Allowed without restrictions
G3
Mains filter may only be loaded with 80% of the maximum allowed
continuous current
G4
Allowed without restrictions
G5
Mains filter may only be loaded with 80% of the maximum allowed
continuous current
Tab. 8-26:
Allowed Mounting Positions
Using mains filters in mains grounded via outer conductor
When using mains filters NFD03 in mains grounded via outer con‐
ductor, use an isolating transformer between mains and mains fil‐
ter.
Number
Mains filter type
of pha‐
ses
(1)
3
NFD
03.1-480-007
3
NFD
03.1-480-016
3
NFD
03.1-480-030
3
NFD
03.1-480-055
3
NFD
03.1-480-075
3
NFD
03.1-480-130
3
NFD
03.1-480-180
Cables, accessories, additional components
Terminal connectors (3)
Flexible
Rigid
AWG
[mm
2
]
[mm
2
]
4 (3)
6 (3)
AWG 12
4 (3)
6 (3)
AWG 12
10
16
AWG 6
16
25
AWG 4
25
35
AWG 3
50
50
AWG 1/0
95
95
AWG 4/0
Bosch Rexroth AG
295/341
Power
Weig
Type of
dissipa‐
ht
construc‐
tion ap‐
tion
prox.
W
kg
3,9
0,7
Vertical
6,4
1,0
Vertical
11,9
1,4
Vertical
25,9
2,0
Vertical
30,4
3,5
Vertical
38
4,7
Vertical
61
10
Vertical

Hide quick links:

Table of Contents
loading

Table of Contents