Appendix - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
11

Appendix

11.1
Dimensioning the line cross sections and fuses
International except for USA/
Canada; installation type B1
Dimensioning the line cross sections and fuses in the supply feeder
and branches to the drive system:
1.
Determine current in supply feeder of drive system
correction factors for
(In the technical data of the components in section "Data for mains volt‐
age supply", you can find standardized data for connection cross sec‐
tion and mains circuit breaker at operation under rated conditions.)
2. Determine country of use ("international except for USA/Canada" or
"USA/Canada")
3. Determine installation type (e.g., B1 or B2)
4. In "Current carrying capacity" table row, select the value that is immedi‐
ately above the value determined in the first step
5. In "Fuse" table row, read corresponding fuse
6. In "Cross section A ..." table row, read corresponding required cross
section
Country of use: international except for USA/Canada
Fuse I
[A]
N
1 ×
2 ×
2
4
6
10
16
16
20
35
35
50
80
100
125
160
200
200
250
250
Bosch Rexroth AG
ambient temperature
and bundling.
Current carrying ca‐
pacity (× 0.87) I
Z(40)
3 ×
[A]
1.6
3.3
5.0
8.6
10.3
13.5
18.27
24.36
31.32
43.50
59.16
77.43
95.70
116.58
148.77
180.09
207.93
227.94
317/341
Appendix
and correct it with
Cross section A [mm
]
2
Installation type B1
1.5
1.5
1.5
1.5
1.5
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150

Hide quick links:

Table of Contents
loading

Table of Contents