Control Cabinet Design According To Interference Areas - Exemplary Arrangements - Bosch Rexroth IndraDrive CsDrive System with HCS01 Project Planning Manual

Hide thumbs Also See for Rexroth IndraDrive CsDrive System with HCS01:
Table of Contents
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
Poorly grounded control cabinet doors can act as antennas. For this reason,
connect the control cabinet doors to the cabinet on top, in the middle and on
the bottom with short equipment grounding conductors with a cross section of
at least 6 mm
2
or, even better, with grounding straps of the same cross sec‐
tion. Make sure connection points have good contact.
Control cabinet design according to interference areas - exemplary ar‐
rangements
Do not operate any additional loads at the mains filter!
Do not run any other loads at the connection from the mains filter
output to the mains connection of the supply unit.
Use separate mains filters for, e.g., motor fans and power supply
units.
Bosch Rexroth AG
173/341
Mounting and installation