General data and specifications
4.3

Installation conditions

4.3.1

Ambient and operating conditions

Description
Conductive dirt contamination
Degree of protection of the device (IEC529)
Use within scope of CSA / UL
Temperature during storage
Temperature during transport
Allowed mounting position
Definition of mounting positions: See
"Mounting positions of components" on page
58
Installation altitude
Ambient temperature range
Bosch Rexroth AG R911335703_Edition 04
Check that the ambient conditions, in particular the control
cabinet temperature, are complied with by calculating the heat
levels in the control cabinet. Afterwards, make the corresponding
measurements to verify that the ambient conditions have actually
been complied with.
In the technical data of the individual components, the power
dissipation is specified as an important input value for calculating
the heat levels.
Devices with the degree of protection IP65 are designed for use near the
machines and are not installed in control cabinets.
Ambient and operating conditions (HCS, HMV, HMS, HMD, HCQ, HCT, KCU,
HLC, HNF)
Symbol
Unit
-
-
-
-
-
-
-
-
-
-
-
-
chapter
h
m
nenn
T
°C
a_work
IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
Value
Not allowed
Protect the devices against conductive dirt
contamination by mounting them in control cabinets
with the degree of protection IP54 (in accordance
with IEC529).
IP20
For use in NFPA 79 Applications only!
See
chapter 4.2.2 "Storing the components" on
page 47
See
chapter 4.2.1 "Transporting the components" on
page 47
G1
3)
1000
0 ... 40