Notes on electrical project planning

7.2.1

Address Selector Switch

WARNING
Before viewing the address, switch off power supply and wait until the 30-
minute discharge time has elapsed. Pull off the connectors form X103.1 and
X103.2 only thereafter.
Set the address for each KSM/KMS with the H and L rotary switches. The
rotary switches are hidden under the X103.1 and X103.2 connector hoods.
H
Address selector switch (×10)
L
Address selector switch (×1)
Fig. 7-22:
Address Selector Switch
Setting
Description
"00"
"00" is the factory setting of the address selector switches.
H = 0
This setting is not applied. The individual drive address must be
set in parameter "S‑0‑1040, Drive address of master
L = 0
communication".
"01" ... "99"
Settings of the address selector switches are applied to
"S‑0‑1040, Drive address of master communication" during the
H = 0 ... 9
booting process.
L = 0 ... 9
Example for setting drive address "14":
Drive address =
H = 1, L = 4 ⇒ drive address = 1×10 + 4 = 14
H×10 + L
See also documentation Parameter Description:
"S‑0‑1040, Drive address of master communication"
"S‑0‑1046, List of slave addresses in device"
"P‑0‑4089.0.3, Device Address"
Tab. 7-9:
Setting the Drive Address at H and L
Notes on project planning
High electrical voltage! Danger to life by
electric shock!