Mounting Position; Mounting Positions Of Components - Bosch rexroth IndraDrive Mi KCU02 Project Planning Manual

Drive systems
Hide thumbs Also See for rexroth IndraDrive Mi KCU02:
Table of Contents
58/407
General data and specifications
4.3.3

Mounting position

Mounting positions of components

Mounting positions
Bosch Rexroth AG R911335703_Edition 04
NOTICE
Only operate the components in their allowed mounting positions. The
allowed mounting positions are specified in the technical data of the
components.
For supply units and drive controllers installed in control cabinets, only the
mounting position G1 is usually allowed.
Some components can also be operated in mounting positions other than G1.
The allowed mounting positions are specified in the technical data of the
component.
The allowed mounting positions are specified with G1, G2, G3, G4 or G5 in
the technical data of the components.
Mounting
Description
position
G1
G2
180° to normal mounting position
G3
90° to normal mounting position
G4
bottom mounting; mounting surface on the bottom
G5
top mounting; mounting surface at the top
Tab. 4-12:
Mounting positions
IndraDrive Mi Drive Systems with KCU02, KSM02,
KMS02/03, KMV03, KNK03, KLC03
Risk of damage to the components by
incorrect mounting position!
Normal mounting position
The air heated inside the component can flow
unimpeded vertically upward. In the case of
components with integrated fans, the natural
convection supports the forced cooling air current.
1.
Mounting surface
2.
Outgoing, heated air
3.
Component
4.
Fan within the component (forces the cooling air
current)
5.
Cooling air
Table of Contents
loading

Table of Contents