Functions that can be executed for know-how protection
The following listed functions can still be executed despite of the fact that know-how
protection is activated:
● Restoring factory settings
● Acknowledging alarms
● Displaying alarms and warnings
● Displaying the alarm history
● Reading out the diagnostic buffer
● Switching over to the control panel (fetch the master control, all the buttons and setting
● Displaying created acceptance documentation
Parameters that can be changed when know-how protection is active
In spite of active know-how protection, certain parameters can be changed and read. The list
of these parameters can be found in the SINAMICS S120/150 List Manual in the Chapter,
Parameters for write protection and know-how protection in the subchapter, Parameters for
write protection and know-how protection/parameters with "KHP_WRITE_NO_LOCK".
Parameters that can be read when know-how protection is active
In spite of know-how protection being active, additional parameters can be read, but are
locked against changes. The list of these parameters can be found in the SINAMICS
S120/150 List Manual in Section Parameters for write protection and know-how protection, in
Subsection "Parameters with KHP_ACTIVE_READ".
Note
Password check for know-how protection
Please note that if the Windows language settings are changed, after activating know-how
protection, errors can occur when subsequently checking the password. If you use language-
specific special characters, you must ensure that the same language setting is active on the
computer for subsequent entry of the password.
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
parameters)
Basic information about the drive system
12.14 Write and know-how protection