Communication With Cbe20; Ethernet/Ip - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents
Communication
10.3 Communication via PROFINET IO
10.3.6

Communication with CBE20

The CBE20 is Communication Board that can be flexibly used and which can be operated
with different communication profiles. Only one firmware of a communication profile can be
loaded at any one time. The available firmware files are saved with the communication
profiles in UFW files on the Control Unit memory card.
The required file is selected using parameter p8835. A POWER ON must be carried out after
selecting the desired UFW file. During the subsequent system boot, the corresponding UFW
file is loaded. The new selection then becomes active.
Table 10- 67 UFW files and selection in the pointer file
UFW file and folder on the memory card
/SIEMENS/SINAMICS/CODE/CB/CBE20_1.UFW
/SIEMENS/SINAMICS/CODE/CB/CBE20_2.UFW
/SIEMENS/SINAMICS/CODE/CB/CBE20_3.UFW
/SIEMENS/SINAMICS/CODE/CB/CBE20_4.UFW
/OEM/SINAMICS/CODE/CB/CBE20.UFW
Identification of the firmware version
Using parameter r8858, the loaded firmware version of the PROFINET interface can be
identified uniquely.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p8835
• r8858[0...39]
10.3.6.1

EtherNet/IP

SINAMICS S120 supports the communication with the fieldbus EtherNet Industrial Protocol
(EtherNet/IP or also EIP). EtherNet/IP is an open standard based on Ethernet, which is
predominantly used in the automation industry. EtherNet/IP is supported by the Open
DeviceNet Vendor Association (ODVA).
For communication with EtherNet/IP, an Ethernet CBE20 option board is required. By setting
p8835 = 4, you can choose the communication profile EtherNet/IP. After POWER ON, the
profile becomes active.
782
CBE20 firmware selection
COMM BOARD read diagnostics channel
Functionality (p8835)
PROFINET device
PN_Gate
SINAMICS Link
EtherNet/IP
Customized
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Pointer file content
1
2
3
4
99
Drive functions

Hide quick links:

Table of Contents
loading

Table of Contents