Motorized Potentiometer - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents
Extended setpoint channel

2.4 Motorized potentiometer

2.4
Motorized potentiometer
This function is used to simulate an electromechanical potentiometer for setpoint input.
You can switch between manual and automatic mode for setpoint input. The specified
setpoint is routed to an internal ramp-function generator. Setting values, start values and
braking with OFF1 do not require the ramp-function generator of the motorized
potentiometer.
The output of the ramp-function generator for the motorized potentiometer is available for
further interconnection via a connector output (e.g. interconnection to connector input
p1070 - CI: Main setpoint, an additional ramp-function generator is then active).
Properties for manual mode (p1041 = 0)
● Separate binector inputs for Raise and Lower are used to adjust the input setpoint:
● Invert setpoint (p1039)
● Configurable ramp-function generator, e.g.:
● Non-volatile storage of the setpoints via p1030.3 = 1
● Configurable setpoint for Power ON (p1030.0)
Properties for automatic mode (p1041 = 1)
● The input setpoint is specified via a connector input (p1042).
● The motorized potentiometer acts like a "normal" ramp-function generator.
● Configurable ramp-function generator, e.g.:
● Non-volatile storage of the setpoints via p1030.3 = 1
● Configurable setpoint for Power ON (p1030.0)
62
– p1035 BI: Motorized potentiometer, setpoint, raise
– p1036 BI: Motorized potentiometer, setpoint, lower
– Ramp-up/ramp-down time (p1047/p1048) referred to p1082
– Setting value (p1043/p1044)
– Activate/deactivate initial rounding (p1030.2 = 1/0)
– Starting value is the value in p1040 (p1030.0 = 0)
– Starting value is the stored value (p1030.0 = 1)
– Activate/deactivate (p1030.1 = 1/0)
– Ramp-up/ramp-down time (p1047/p1048)
– Setting value (p1043/p1044)
– Activate/deactivate initial rounding (p1030.2 = 1/0)
– Starting value is the value in p1040 (p1030.0 = 0)
– Starting value is the stored value (p1030.0 = 1)
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions

Hide quick links:

Table of Contents
loading

Table of Contents