Transmitter Activated By Dry Contacts - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
Model IFP-2000/ECS Installation Manual
4.
Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible
rating.
Figure 4-46 Polarity Reversal Connection Using the 7644
4.14.5

Transmitter Activated by Dry Contacts

This section describes the connection of a UL 864 listed remote station transmitter to the IFP-2000 dry relay
contacts. The IFP-2000 FACP contacts must be supervised by the remote station transmitter module using end-
of-line resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the
remote station transmitter manufacturer. Refer to the remote station transmitter manufacturer's manual for
details.
Figure 4-47 Transmitter Activated by Dry Contacts
4-37
151430-L8
Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-2000ecsFarenhyt rps-2000

Table of Contents