Model IFP-2000/ECS Installation Manual
Note: The B200S Sounder base is intended to be used along with the CO cadence setting.
Local Zone (choose Y or N, for Yes or No).
9.3.2

View Zone Points

To view the points in a zone, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 2 to enter zone menu.
4.
Press 2 to view zone points.
5.
Enter the number of the zone you wish to view, then press ENTER.
9.4

Group

An output group is made up of output points that have been programmed to respond in the same way. Output
groups simplify programming because you only have to program the output characteristics that are common to
all of the group points once, instead of programming each individual point. Once you have defined the
characteristics of output groups, you can assign each point to the appropriate group. All valid output points are
assigned to only one output group. Unused points are not assigned to any output group. Up to 999 output groups
can be defined per panel.
Each output group is defined as either a voice output group or a non-voice output group. Output points that are
audio circuits (all circuits on the ECS-50W, ECS-125W, ECS-INT50W, ECS-DUAL50W, and ECS-CE4) can
only be assigned to voice output groups. Output points that are non-voice circuits (all other points and circuits
that are on all modules except the ECS-50W, ECS-125W, ECS-INT50W, ECS-DUAL50W, and ECS-CE4) are
assigned to non-voice output groups.
Note: Adding a Group or Deleting a Group can only be done using SKSS-2. (Silent Knight Software Suite PN 5655).
9.4.1

Edit Group

In the edit group option you can program the name of an output group (Section 9.4.1.1) and change the properties
(Section 9.4.1.2) of that group.
To edit a group, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 1 to edit group.
5.
Enter the number of the group you wish to edit, then press ENTER.
9-7
Zone Number
Figure 9-2 View Zone Points Screen
Zone Name
151430-L8