Adding A Module; Deleting A Module; View Module List; Zone - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
Model IFP-2000/ECS Installation Manual
9.2.2

Adding a Module

To add a new hardware module to the system, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1.
Select 7 for Panel Programming.
2.
Press 1 to enter module menu.
3.
Press 2 to add a module.
4.
From the next screen, select the number that corresponds to the type of module you are adding from the
screen.
The screen will display "Adding module [#]..." for a few moments. You will be returned to the
ule Type> screen where you can add additional modules if desired.
You must save changes when you exit the Panel Programming or the new module will not be added.
Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it reinitializes (when
you exit the Panel Programming). When the new module is attached, the trouble will correct itself automatically the
next time you power up the system.
9.2.3

Deleting a Module

To delete a module, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1.
Select 7 for Panel Programming.
2.
Press 1 to enter module menu.
3.
Press 3 to delete a module.
4.
Select the module to be deleted.
5.
A warning screen will display. If you want to proceed with deleting the module, select Yes. To cancel, select
No.
9.2.4

View Module List

To view a list of all modules, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1.
Select 7 for Panel Programming.
2.
Press 1 to enter module menu.
3.
Press 4 to view list. Use the Up or Down arrow to scroll though list.
9.3

Zone

Through the zone option in Panel Programming you can edit, add, delete, and view zone points. Selections made
here affect all detectors and switches in the zone. Up to 999 zones can be used in each panel.
Note: Adding a Zone or Deleting a Zone can only be done using SKSS-2 (Silent Knight Software Suite PN 5655).
9-3
151430-L8