Sia - Intelliknight / Ifp-2000 Panels Pi Modifier Reporting - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
Model IFP-2000/ECS Installation Manual
12.3 SIA - IntelliKnight / IFP-2000 Panels PI Modifier
Reporting:
Events are sent to the central station as a variable length string:
The event format is:
EEZZZZ
Where:
EE
Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1.
The account number is sent using an account block that is separate from the event block
2.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
3.
Event parameter can be either a zone, point or module number.
4.
When reporting by point is enabled, the dialer uses a "pi" event to supersedes the actual point event to report
the module the point is linked to.
5.
Panel ID is not sent in the SIA event parameters.
For Example see Table 12-2:
Table 12-2: SIA- IntelliKnight / IFP-2000 Panels - PI Modifier Reporting Examples
Event
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander
18
SLC Loop Shorted
Program Begin Panel
ID=32
Program Begin Panel ID=
22
AC Power Loss - Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-Nac
12-13
Zone
n/a
n/a97
15
Zone
n/a
n/a
05
Point
n/a
01
n/a
Point
n/a
33
n/a
n/a
n/a
11
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
n/a
18
n/a
n/a
n/a
44
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
n/a
Point
n/a
97
n/a
Zone
n/a
97
01
Point
n/a
98
n/a
n/a
EE-ZZ
FA15
n/a
EE-Z
FA5
123
EE-ZZ /EE-
pi01/FA123
ZZZ
203
EE-ZZ /EE-
pi11/FA203
ZZZ
n/a
EE-ZZ
ET11
n/a
EE-Z
RP0
n/a
EE-ZZ
YT98
n/a
EE-ZZ
YT18
n/a
EE-ZZ
ET44
n/a
EE-Z
LB0
n/a
EE-Z
LB0
n/a
EE-Z
AT0
200
EE-ZZ /EE-
pi97/FT200
ZZZ
n/a
EE-Z
FT1
Nac
EE-ZZ /EE-
pi98/FT7
Circuit 7
Z
Z=Pt. #
151430-L8