Double Interlock Zone Releasing - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
151430-L8
10.7.2

Double Interlock Zone Releasing

A Double Interlock Zone uses a minimum of two addressable detectors, a designated manual release switch, and
an interlock switch input. An interlock switch is typically a dry-contact pressure switch and will be referred to as
an interlock/pressure switch in this document.
Only addressable detectors can be used. No conventional detectors can be used.
Each Double Interlock Zone input requires at least one Interlock/pressure switch and at least one manual release switch.
Conditions Required for a Interlock Release Alert Output Activation
If any single addressable detector is activated, the "Interlock Release Alert" output will activate. This alerts the
user that the initial stages required for a release condition are present. (Also refer to Table 10-5).
Conditions Required for a Detector Alarm Output Activation
If two addressable detectors, a manual release switch is activated, or an interlock switch is active, the "Interlock
Release Alert", and "Detector Alarm" outputs will activate.
Conditions Required for a Interlock Release Alarm Output Activation
Any release requires the activation of an interlock switch, and either a manual release switch or 2 activated
addressable detectors. When these conditions are met, the "Interlock Release Alarm" and "Detector Alarm"
outputs will activate, and the "Interlock Release Alert" outputs will deactivate.
Inputs
X
1st Addressable
Detector
2nd Addressable
Detector
Manual Release
Station
Interlock/
Pressure Switch
Important!
Table 10-5 Double Interlock Zone Operation
X
X
X
X
X
X
X
X
10-18
Output Results
X
X
X
X
X
X
X
X
X
X
X
System Operation
X
X
X
X
X
X
X
X
X
X
X
X