Smoke Alarm Verification; Function Keys; Recording An F-Key Macro; Aborting An F-Key Macro Recording Session - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
Model IFP-2000/ECS Installation Manual

10.8 Smoke Alarm Verification

Figure 10-8 illustrates how the Smoke Alarm Verification cycle operates.
During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
10.9

Function Keys

The function keys on the IFP-2000 have multiple features. Their macro key functionality can simplify the
disabling, activating, or inhibiting points or groups respectively. They can also be used as a status type activation
event and for activating Map Inhibit. Each F-Key macro can hold 50 events.
To access the F-Key Recording menu:
1.
From the idle screen, press and hold the F-Key for 5 seconds.
2.
Enter a PIN with F-Key macro recording privileges, if prompted.
10.9.1

Recording an F-Key Macro

1.
Access the F-Key Recording menu and select the 'Start FKEY Recording' option.
2.
The panel will return to the idle screen. Notice the 4th line on the display now alternates with
Recording>, where # is the number of the F-Key being recorded.
3.
Any Disabling or Activating of points, output groups, or templates from the site at this point will be pro-
grammed into the macro. Do this by going to any annunciator within the site and entering Main Menu ->
Point Functions and use Disable/Enable Point or use I/O Point Control to: disable output groups or individ-
ual points, or activate individual points.
4.
Once you are finished with disabling or activating points/output groups, enter the F-Key Recording Menu
again and select the 'End FKEY Recording' option.
5.
The panel will return to the idle screen.
10.9.2

Aborting an F-Key Macro Recording Session

1.
After an F-Key macro recording session has been started, the session can be canceled at any time by access-
ing the F-Key Recording menu and selecting 'Abort FKEY Recording' option.
2.
The panel will return to the idle screen.
Figure 10-8 Smoke Verification Cycle
10-19
151430-L8