than 100 mA of current is allowed to flow into the open collector transistor.
Figure 4-24 5880 Board Layout
4.8.4

Dry Contact Wiring

The 8 input circuits on the 5880 board are for monitoring switch inputs. Any type of switch supported by the
control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow,
tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-25. Notice grouping of terminals; power terminals are shared by two
inputs.
Supervised
Model 7628
EOL Resistor
Figure 4-25 Dry Contact Wiring
4-19