Operation Mode Behavior - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
151430-L8
Manual Pull is mapped to Voice Group 1 as an Alert 1 mapping and Zone 2 Manual Pull is mapped to Voice
Group 1 as a normal mapping. If Zone 1 and Zone 2 Manual Pull events are active, Voice Group 1 will
annunciate the Fire Alarm message defined in the Voice Settings for the panel's assigned site.
Event priority is considered here based on the Event Priority Table.
If an output group is mapped both directly and through an output group template to an event, the direct map
gets priority. Example: Template 1 Contains Group 1. Zone 1 Manual Pull is mapped to Template 1 and
Group 1 using constant and ANSI patterns respectively. If Zone 1 Manual Pull is active, Group 1 will output
ANSI.
When an event is mapped to an output group from multiple zones, the lower numbered zone gets priority.
Example: Zone 1 Manual Pull and Zone 2 Manual Pull are mapped to Group 1 using constant and ANSI
patterns respectively. If Zone 1 and Zone 2 Manual Pull events are active, Group 1 will output constant.

10.6 Operation Mode Behavior

The control panel can be in one or more of seven conditions at any given moment: Normal, Alarm, Prealarm,
Supervisory, Trouble, Silenced, and Reset. Table 10-2 describes the behavior of the panel in each of these modes.
When looking at the LCD, the screen will display FS for the "Fire System", CO for the "CO System" and ECS
for "Emergency Communication System". The highest priority event will display first and include the event
count (see Figure 10-4).
Press the down arrow to view the location and type of alarm supervisory or trouble. If the panel is programmed to
Auto Display Event, information describing the highest priority active event will display on the first two lines.
The 3 and 4th line will show the status of which event types are active for each system (fire, CO and emergency
systems). Auto Display Event activates after two minutes of annunciator inactivity. (See Figure 10-5).
Count of fire system
alarms currently active
Count of CO
alarms
currently
active
Figure 10-4 Highest Priority Event Display
10-10
System Operation
Count of emergency
communication system
alarms currently active