Point Programming For 5880/5865 Modules - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
151430-L8
9.5.3

Point Programming For 5880/5865 Modules

To program the 5880/5865 module output points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrows to select the desired module. Refer to Section 8.6 for available choices. Then
press ENTER.
Select an output Group
for this Zone/Group
Select a name
for the Point
Figure 9-5 Programming Points as Outputs for the 5880 Module
Figure 9-6 Programming Points as Inputs for the 5880 Module
5.
Enter the point number, then press ENTER.
6.
Press the Up or Down arrows to select the type (notification or unused)., then press ENTER.
7.
Press the Up or Down arrows to select the desired group., then press ENTER.
8.
Press ENTER to edit point name. See Appendix B.
Or
Press the right arrow to skip point name edit.
9.
Repeat Steps 1 through 8 for all output points.
10. To use 5880 as Input point, Enter point number 41 - 48. (See Figure 9-6 on page 16). Then press ENTER.
11. Press the Up or Down arrows to select type (switch or unused), then press ENTER.
12. Press the Up or Down arrows to select the desired function. (See Figure 9-5 on page 19), then press ENTER.
13. If the point supports latching press the Up or Down arrows to select latching or non-latching, then press
ENTER.
14. Press the Up or Down arrows to select the desired group/zone, then press ENTER.
15. Edit point name Or Press the right arrow to skip module name edit.
16. Repeat steps 10 through 15 for all input points.
Select NOTIF
Enter Point
or Unused
Select Switch or Unused
Select Function
9-16
Programming