Point Programming For Ecs-Vcm Or Ecs-Rvm - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
151430-L8
8.
Repeat Steps 1 through 7 for all points.
9.5.6

Point Programming for ECS-VCM or ECS-RVM

To program module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrow to select the desired module. Refer to Section 8.6 for available choices. Then
press ENTER.
Select a name
for the Point
Figure 9-9 Programming Points Screen for the ECS-VCM or ECS-RVM Modules
5.
Enter the point number. Press ENTER.
6.
Press the Up or Down arrow to select the type (switch or unused). Press ENTER.
7.
Press the Up or Down arrow to select the desired Function (See Table 9-5). Press ENTER.
8.
Press ENTER to edit point name. See Appendix B. Or Press the right arrow to skip point name edit.
9.
Repeat Steps 1 through 8 for all points.
Enter Point
Select NOTIF
or Unused
9-18
Programming