Edit Banner; Edit Slc Family; Edit Ethernet - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
Model IFP-2000/ECS Installation Manual
9.6.8

Edit Banner

The banner is the message that displays on the panel LCD when the system is normal; that is, when no alarms or
troubles exist and the system menus are not in use. A custom banner of up to 40 characters can be created. This
will automatically be centered when shown.
If a custom message is not created, the system will use the internal banner. You cannot change the internal
banner.
To customize the banner display message:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
Select 7 for Edit Banner.
Note: See Appendix B for instructions on how to edit the banner.
5.
Select each letter by pressing the Up or Down arrow to change modes and using the number keys to select
characters, then press the right arrow to move to the next character.
6.
When done, press ENTER to save the custom banner.
9.6.9

Edit SLC Family

The IFP-2000 supports SD series SLC devices or IDP (Intelligent Device Protocol) series SLC devices. You
must configure the IFP-2000 to accept the family of the devices you are installing. You cannot mix SD series and
IDP series SLC devices on the same panel.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Press 8 for SLC Family.
5.
Press UP arrow to select the desired SLC family.
6.
Press ENTER to accept the displayed SLC family.

9.6.10 Edit Ethernet

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
9-27
151430-L8
Table of Contents
loading

This manual is also suitable for:

Farenhyt ifp-2000ecsFarenhyt rps-2000

Table of Contents