Model IFP-2000/ECS Installation Manual
10.4.6

Conduct a Walk Test

1.
From the Main Menu, press 1 for System Tests.
If any alarm verification zones are being used, the user will be asked if they wish to disable alarm
verification during walk test. This occurs for either walk test option.
2.
Select 3 for Walk Test-No Report. The LCD will display "WALK TEST STOPPED" on Line 1 and "ENTER
= start test" on Line 3. Enter the time period you wish the NAC circuit to be active for each alarm (06 to 180
second), if you select this option, central station reporting will be disabled while the test is in progress.
Or
Select 4 for Walk Test-with Report. The LCD will display "WALK TEST STOPPED" on Line 1 and
"ENTER = start test" on Line 3. Enter the time period you wish the NAC circuit to be active for each alarm
(06 to 180 seconds) If you select this option, central station reporting will occur as normal during the walk
test.
The panel generates a TEST report to the central station when the walk test begins. During a walk test, the
panel's normal fire alarm function is completely disabled, placing the panel in a local trouble condition. All
zones respond as 1-Count zones (respond when a single detector is in alarm) during a walk test. Each alarm
initiated during the walk test will be reported and stored in the event history buffer.
3.
Press ENTER to end the walk test. The system will reset. The panel will send a "TEST RESTORE" report to
the central station.
If you do not end the walk test manually within four hours, it will end automatically.
If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the walk test.
Note: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the
panel is ready to go to the next device.
10.4.7

Conduct a Dialer Test

1.
From the Main Menu, press 1 for System Tests.
2.
Select 5 for Dialer Test. The screen will display "Manual dialer test started". When the test is completed, you
will be returned to the . A manual dialer test requires that at least one daily test in the network
be enabled in dialer programming.
10.4.8

Silence Alarms or Troubles

Press SILENCE to turn off silenceable outputs and annunciator PZTs. If an external silence switch has been
installed, activating the switch will silence fire alarms or troubles. If you are already using system menus when
you press SILENCE, you will not need to enter your code.
Note: Alarm and trouble signals that have been silenced, but the detector remains un-restored, will un-silence every 24 hours
until the detector is restored.
Note: Multi-Site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the PZT built
into the annunciator. To silence a site, enter a multi-site access password, select a site, and then press SILENCE.
Note: For ECS systems, pressing silence at an LOC will only silence the System in Control. See Section 10.5.1.
10.4.9

Reset Alarms

Press RESET to perform a control panel reset. If an external reset switch has been installed, activating the switch
will reset fire alarms.
Note: Multi-Site displays do not allow for resetting multiple sites. To reset a site, enter a multi-site access password, select
a site, and then press RESET.
Note: For ECS systems, pressing reset at an LOC will prompt the user for which system they desire to reset. See Section
Important
10-5
151430-L8