Time Options; Water Flow Delay; Alarm Verification Time; Low Ac Report Delay - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
151430-L8
9.6.5

Time Options

Through this programming option you can set the water flow delay time, alarm verification time, low AC report
delay, AC line frequency, and clock format.
9.6.5.1

Water Flow Delay

You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
Select 4 for Time Options.
A screen similar to the one shown in Figure 9-13 will display.
5.
Enter the number of seconds (0 to 90) to delay a water flow switch alarm, then press ENTER.
9.6.5.2

Alarm Verification Time

You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow
9.6.5.3

Low AC Report Delay

Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a low AC report will be sent to the central station.
To program low AC report delay, follow these steps:
Note: Steps continued from step 7 of Section 9.6.5.2.
Figure 9-14 Low AC Report Delay Programming Screen
Delay in seconds before waterflow
alarm occurs (00-90)
Figure 9-13 Water Flow Delay Programming Screen
ENTER to make your selection and move to the next programming option.
or
Low AC Report
Delay in Hours
(00-30)
9-24
Programming